741 - Outdoor unit CCVIBA - Heat pump
Description:
The equipment constituing the series CCVIA/ECVIA - CCVIBA/ECVIBA are vertical air conditioner units, in split building, being the first cooling only and the second heat pump. In parallel and compact building there are available the models ACVIA-ACVIBA, both manufactured in version cooling or heat pump, and are suitable to operate coupled to a duct air distribution both in the inner section and outer.
Cabinet:
Manufactured in galvanized steel, finished with polyester resins, polymerized in the oven, excellent resistance to corrosion and in the open. The set is lined with thermoacoustic insulation.
Compressors:
-Scroll type
-Motor type: BLDC.
-Number of poles: 6
-Supply: Triphase.
Brushless motor comprises a stator and a rotor with permanent magnets. Has a higher efficiency than an induction motor because there is no losses magnetization current in the rotor.
Exchanger:
Made of aluminum fin (fin space 1.8 mm) and copper tube 3/8 expanded mechanically, exchange high performance.
Expansion device:
As much divide as compact models are equipped as standard with Electronic Expansion Valves. In the case of compact models are assembling a single compact Expansion Valve whereas divide models incorporate one for each section. For divide models altough the assembly is composed for two Electronic Expansion Valves only regulates the selection corresponding to the exchanger which is vaporizing, remaining fully open the other valve.
Air filtre:
Polyurethane foam, washable, 10 mm. thick crosslinked S-20 with high efficiency filtration.
Fans:
-Centrifuge type.
-Supply by frecuency converter.
-Variable airflow condenser.
-Three evaporator air flow (Low, Medium and High Speed)
-Evaporator possibility of increasing or decreasing the available pressure.
Cooling circuit:
-Built in special copper tube for refrigeration, dehydration, incorporating drying filter and check valve with an easy acces for verification and load.
-Equip suction accumulator on the compressor suction line, protecting it from liquid slugging.
-Split models include as well oil separator.
-Reversing valve for cycle inversion activated by solenoid at 230 volts in heat pump models.
-Unidirectional valves.
-The welds between the different elements are executed with copper-silver alloy.
Operate and control equipment
Each unit has these control and safety devices:
-Environtment thermostat to 230 Volts c.a.monophase.
-Magnetothermic of protection for compressor, ventilation and operating general motors.
-Speed regulator for the fan motor outer side (both cooling and heat pump).
-Thermical protection of triphase motors of fans.
-High pressure switch with manual reset.
-Defrost system control pressure according to predetermined periods of operation time.
-Reversing valve activated by solenoid at 230 volts.
-ON-OFF remote connection and heat-cool
-Alarm Signal.
Maximum cooling capacity (120 Hz) kW 23,9
Maximum cooling capacity (120 Hz) T.R. 6,8
Maximum heating capacity (120 Hz) kW 25,8
Nominal cooling capacity (80 Hz) kW 17,7
Nominal cooling capacity (80 Hz) T.R. 5
Nominal heating capacity (80 Hz) kW 17,8
Maximum EER coefficient kW/kW 2.86
Maximum COP coefficient kW/kW 2.94
Power supply (50 Hz ~) V 400.3+N
Cooling connect. Liquid line Ø () 5/8
Cooling connect. Gas line Ø () 11/8
Max out. airflow - static pressure m3/h - Pa 7300 - 80
Dimensions (length x width x height) mm 1130x800x1250
Net weight Kg 320
741 - Indoor unit ECVIBA - Heat pump
Description:
The equipment constituing the series CCVIA/ECVIA - CCVIBA/ECVIBA are vertical air conditioner units, in split building, being the first cooling only and the second heat pump. In parallel and compact building there are available the models ACVIA-ACVIBA, both manufactured in version cooling or heat pump, and are suitable to operate coupled to a duct air distribution both in the inner section and outer.
Cabinet:
Manufactured in galvanized steel, finished with polyester resins, polymerized in the oven, excellent resistance to corrosion and in the open. The set is lined with thermoacoustic insulation.
Compressors:
-Scroll type
-Motor type: BLDC.
-Number of poles: 6
-Supply: Triphase.
Brushless motor comprises a stator and a rotor with permanent magnets. Has a higher efficiency than an induction motor because there is no losses magnetization current in the rotor.
Exchanger:
Made of aluminum fin (fin space 1.8 mm) and copper tube 3/8 expanded mechanically, exchange high performance.
Expansion device:
As much divide as compact models are equipped as standard with Electronic Expansion Valves. In the case of compact models are assembling a single compact Expansion Valve whereas divide models incorporate one for each section. For divide models altough the assembly is composed for two Electronic Expansion Valves only regulates the selection corresponding to the exchanger which is vaporizing, remaining fully open the other valve.
Air filtre:
Polyurethane foam, washable, 10 mm. thick crosslinked S-20 with high efficiency filtration.
Fans:
-Centrifuge type.
-Supply by frecuency converter.
-Variable airflow condenser.
-Three evaporator air flow (Low, Medium and High Speed)
-Evaporator possibility of increasing or decreasing the available pressure.
Cooling circuit:
-Built in special copper tube for refrigeration, dehydration, incorporating drying filter and check valve with an easy acces for verification and load.
-Equip suction accumulator on the compressor suction line, protecting it from liquid slugging.
-Split models include as well oil separator.
-Reversing valve for cycle inversion activated by solenoid at 230 volts in heat pump models.
-Unidirectional valves.
-The welds between the different elements are executed with copper-silver alloy.
Operate and control equipment
Each unit has these control and safety devices:
-Environtment thermostat to 230 Volts c.a.monophase.
-Magnetothermic of protection for compressor, ventilation and operating general motors.
-Speed regulator for the fan motor outer side (both cooling and heat pump).
-Thermical protection of triphase motors of fans.
-High pressure switch with manual reset.
-Defrost system control pressure according to predetermined periods of operation time.
-Reversing valve activated by solenoid at 230 volts.
-ON-OFF remote connection and heat-cool
-Alarm Signal.
Maximum cooling capacity (120 Hz) kW 23,9
Maximum cooling capacity (120 Hz) T.R. 6,8
Maximum heating capacity (120 Hz) kW 25,8
Nominal cooling capacity (80 Hz) kW 17,7
Nominal cooling capacity (80 Hz) T.R. 5
Nominal heating capacity (80 Hz) kW 17,8
Maximum EER coefficient kW/kW 2.86
Maximum COP coefficient kW/kW 2.94
Power supply (50 Hz ~) V 400.3+N
Cooling connect. Liquid line Ø () 5/8
Cooling connect. Gas line Ø () 11/8
Indoor airflows m3/h 3200/3800/4800
Max out. airflow - static pressure m3/h - Pa 4800 - 75
Dimensions (length x width x height) mm 1130x800x650
Net weight Kg 150